How can we help you today?
How do you wire a external 24vdc digital output from a PLC to the input of the ATV21 or 212 drive?
Resolution:
Make sure the Source, CLP, Sink dip switch is set to CLP.
Example of PLC with a sourcing output.
ON the ATV21 or ATV212 drive jumper PLC and CC together. Then wire the PLC and CC to 0V on the external PLC or Power supply.
Next run your external 24vdc digital output from your PLC controller to the F, R or RES inputs of the drive.
Example of PLC with a sinking output.
On the ATV21 or ATV212 drive jumper CC to 0V and jumper the ATVs PLC connection to external +24vdc supply.
The PLC controllers output will wire to F, R, RES inputs of the drive.
See attachment for example
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.