How do I program my ATV21 or ATV212 for BACnet communication?
Resolution:
BACKGROUND:
BACnet is an open Communication Protocol that was developed by ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers).
This is a link to the BACnet Website: http://www.bacnet.org/index.html
Schneider Electric Drives support only the MS/TP version of BACnet. MS/TP. This is a 2-wire RS485 based network protocol, similar to ModBus.
Other vendors may support BACnet over Ethernet and Arcnet. (don’t be surprised if we do offer an Ethernet option in the future).
Usually the BACnet (controller) communicates to several different routers or bridges over Ethernet (called BACnet IP) or ArcNet, and these devices are connected via the 2 wire RS485 hardwire connection to our drives.
ATV212 implementation of BACnet:
Hardware:
The ATV212 has 4 embedded communication protocols, selected via programming (ModBus, Apogee P1, Metasys N2, and BACnet).
Lonworks option available (Part Number VW3A21212)
A is –
GND is Ground (actually signal common)
B is +
SCR is Shield
Programming in the Drive:
F829 (Network Protocol): Set to 4 for BACnet Communications
F890 (Network Address): Set the network address from 0 to 127.
F891 (Network Baud Rate): Sets the speed of communication between the drive and the master. Options are 1 = 9600, 2 = 19200, 3 = 38400, 4 = 76800. Default is 5 = AUTO (where the drive attempts to detect the network baud rate). All devices on the RS485 network must communicate at the same Baud Rate.
Format: This is fixed at 8-N-1. Stands for 8 Data bits, No Parity, and 1 Stop bit. All devices on the RS485 network must be set to the same format.
F892 (Network Time-Out): Adjustable between 2 to 60.0 seconds (20 to 600 tenths). Sets the time before the drive will “Time Out” indicating a loss of communication with the controller.
F893 and F894 (Instance Number): F893 is adjustable between 0 and 4194. F894 is adjustable between 0 and 999.
Example: If F893 is 0235 and F894 is 0045 the Instance number is 0235045.
This must be unique for each device on the network, and we recommend it be set higher than the Address. This is also known as the BACnet device ID.
F895 (Max M): Adjustable between 0 and 127. Sets the Maximum number of devices allowed on the network. Reducing this number can improve network speed and data through put.
F896 (Max Info Frames): Adjustable between 1 and 100. Sets the time period (# of Frames) that the drive “owns” the Token. Lower numbers will increase network speed, but may not allow the drive to update all parameters on one scan. Higher numbers will allow full data transfer, but slower update times. Factory default is 1. We recommend this be set to 10.
FA15 (Communication Counter): Read Only. Displays the total number of Frames received by the drive sine the last power on. If this number is very low, or not increasing, then it indicates network problems. (Can only be seen in HMI or Using SOMOVE)
FA16 (Normal Communication Counter): Read Only. Displays the number of bad frames received since the last power on. If this number is High or increasing rapidly it indicates network problems. (Can only be seen in HMI or Using SOMOVE)
Consult the ATV212 BACnet manual for details (ATV21 BACnet manual is available on our website).
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.