Is there a deadfront filler plate for an NQMB** kit used in a NQ442L2 panel if the main breaker is removed and the main lugs are used?

Article available in these languages: Spanish

Issue:
What is the deadfront filler plate for a vacated Main breaker in a NQ442L2 panel ?

Product Line:
NQ Panelboards

Environment:
Maintenance

Cause:
Coverting Main breaker to Main lug Panel

Resolution:
The previously offered closing plate, part no. 80103-079-02, is now obsolete and no longer available.
A NQXXRDE  Rail extension kit can be used, (Where X is the length of the blank dead front and rail extensions, ie NQ12RDE for 12" H).

This rail extension kit is used to make up the difference between a MLO box height and the MCB height Box.
It also can be used after the Main breaker is removed and converted to a Main lug interior. The Blank deadfront has no openings where the Main was originally .

See attached instruction Bulletin

Schneider Electric USA

Attachment(s)
NQ Rail ext inst bulletin 80043-732-02.pdf [7.07 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings