Is there a deadfront filler plate for an NQMB** kit used in a NQ442L2 panel if the main breaker is removed and the main lugs are used?
Issue:
What is the deadfront filler plate for a vacated Main breaker in a NQ442L2 panel ?
Product Line:
NQ Panelboards
Environment:
Maintenance
Cause:
Coverting Main breaker to Main lug Panel
Resolution:
The previously offered closing plate, part no. 80103-079-02, is now obsolete and no longer available.
A NQXXRDE Rail extension kit can be used, (Where X is the length of the blank dead front and rail extensions, ie NQ12RDE for 12" H).
This rail extension kit is used to make up the difference between a MLO box height and the MCB height Box.
It also can be used after the Main breaker is removed and converted to a Main lug interior. The Blank deadfront has no openings where the Main was originally .
See attached instruction Bulletin
What is the deadfront filler plate for a vacated Main breaker in a NQ442L2 panel ?
Product Line:
NQ Panelboards
Environment:
Maintenance
Cause:
Coverting Main breaker to Main lug Panel
Resolution:
The previously offered closing plate, part no. 80103-079-02, is now obsolete and no longer available.
A NQXXRDE Rail extension kit can be used, (Where X is the length of the blank dead front and rail extensions, ie NQ12RDE for 12" H).
This rail extension kit is used to make up the difference between a MLO box height and the MCB height Box.
It also can be used after the Main breaker is removed and converted to a Main lug interior. The Blank deadfront has no openings where the Main was originally .
See attached instruction Bulletin
Released for: Schneider Electric USA
Attachment(s)
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.