Video: How to Reset ATV212 or ATV21 Drives to Factory Defaults

Article available in these languages:

Resolution:
Set tYP = 3 to return to factory settings (remember to press and hold enter for 2 seconds).
Then set  tYP = 2 to configure for 60Hz.
Proceed with any further programming from here.

ATV212 Typ parameter

Consult the ATV212 Programming Manual or ATV21 Programming Manual for additional details: