Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the assignments for the output relays on an ATV212 ?

Article available in these languages: Thai

Issue:
ATV212 output relays assignments.

Product Line:
ATV212

Environment:
Output relays

Cause:
n/a

Resolution:
FLA, FLB, FLC are the terminals for a single pole, double throw (Form C) relay and the default assignment is ``inversion of fault relay``.  Off = drive faulted, On = no drive fault.  Parameter F132 can be used to change this relay function.

RYA, RYC are terminals for a single normally open contact (Form A) and the default setting is ``speed attained``.  The relay contact closes when the hertz value assigned to F100 is reached.  F100 is defaulted to 0.  A common customer request is for ``drive running``.  Parameter F130 can be assigned to 14 for ``drive running``.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings