On an ATS48, how is the R1 relay set to control an isolation contactor?
Issue:
How to set R1 to control an isolation contactor in SoftStarter ATS48?
Product Line:
Variable Speed Drives and Soft Starters
Environment:
Soft Start - Altistart 48
Resolution:
From the display status screen, typically rdY or nLP, arrow down to the IO menu and ENT. Arrow to parameter r1, ENT and change to R1I. ENT to save.
How to set R1 to control an isolation contactor in SoftStarter ATS48?
Product Line:
Variable Speed Drives and Soft Starters
Environment:
Soft Start - Altistart 48
Resolution:
From the display status screen, typically rdY or nLP, arrow down to the IO menu and ENT. Arrow to parameter r1, ENT and change to R1I. ENT to save.
Released for: Schneider Electric USA