How can we help you today?

What is an O.CF fault on an ATV31 or ATV312 drive?

Article available in these languages:

  • Czech
  • , Spanish

Issue:
O.CF fault on an ATV31 or ATV312

Product Line:
Altivar, ATV31, ATV312

Environment:
All

Cause:
N/A

Resolution:
O.CF is a phase-to-phase motor short circuit fault.  Check motor windings and motor leads for a possible shorting path. A Megger test at a 1,000V of the motor and motor leads should be performed.
You can also try running the drive "open circuit" and see it faults without the motor connected
1. ​Turn off Output Phase Loss (OPL)
2. Power down and disconnect the motor leads from the drive
3. Run the drive at 20, 40, and 60Hz and measure output voltage phase-to-phase checking for balanced voltage

Other possible related fault codes are OCF and OC.F:
OCF is an overcurrent fault.  Possible causes are incorrect settings in the SET and DRC menus, excessive loading on the motor or mechanical binding.
OC.F is an impedance short-circuit fault.  This is a detected short-circuit or grounding at the drive output. Check the cables connecting the drive to the motor and the motor insulation.  A Megger test at a 1,000V of the motor and motor leads should be performed.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings