Is there a way to get more torque out of the motor when running at lower speeds with an ATV312 drive?
Issue:
How to increase the torque out of a motor when running at lower speeds with an ATV312 drive
Product Line:
ATV312
Environment:
All
Cause:
More torque
Resolution:
First, verify that the motor data is correct in the drC menu. Then set UFt to L. In the SEt menu, increase UFr to provide higher torque output.