How can running frequencies be skipped in an ATV61/ATV71 ?

Article available in these languages:

  • Spanish

Issue:
Skipping output frequencies in an ATV61/ATV71

Resolution:

The Skip Frequency function allows an ATV61 or ATV71 drive to avoid operating at specific motor speeds that may cause resonance, vibration, or excessive noise.

To configure a skip frequency, navigate to Menu 1.3 - Settings and adjust the following parameters:

  • Skip Frequency (JPF): Sets the center frequency of the range to be skipped.
  • Skip Frequency Hysteresis (JFH): Defines how many hertz (Hz) above and below the center frequency will be excluded.

The skipped frequency range is calculated as:

(JPF - JFH) to (JPF + JFH)

Note: The JFH hysteresis applies to all three skip frequency parameters: JPF, JF2, and JF3.

Example

  • JPF = 30 Hz
  • JFH = 2 Hz

The drive will avoid operating between 28 Hz and 32 Hz:

  • Lower limit: 30 - 2 = 28 Hz
  • Upper limit: 30 + 2 = 32 Hz

This setting helps prevent operation within frequency ranges that can create unwanted motor resonance, vibration, or noise.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings