Why will ATS01N2 Softstart not run the motor when powered?
Issue:
Why is the ATS01 not running the motor when power is applied?
Resolution:
The ATS01N2**LU/QN/RT models require a run command on the control circuit.
A START/STOP contact can be wired to LI+ and LI2. This will allow soft start and soft stop.
If the softstarter is to run the motor when power is applied to the ATS01, then install a jumper between LI+ and LI2. This will give a soft start and a freewheel stop.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.