Can I run an ATS softstarter without a motor load or motor connection?

Article available in these languages:

  • Korean


Soft Starts require a load in order to operate properly.
Softstarts use SCR's to switch the voltage on and off to the motor.
An SCR requires current flow to operate properly.  With no load, there is no current flow.
With no current flow, the soft starter will fault with PHF fault when the run command is given.

On the ATS48 and ATS480 models of soft start, it is possible to run the soft start with an undersized motor, for testing only.

Parameter SST, under the Advanced Settings menu can be set to ON.  This will allow the starter to be run with a motor as small as 10% of the rating of the starter.

Note:
• SSt returns to the OFF state as soon as the control voltage is disconnected. On the next
power up, the PHF fault and the CLP parameter return to their initial configuration.
• SST is only dedicated for maintenance and testing of the starter.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings