Is a line reactor required with the ATV61 or ATV71 drives if the DC choke is not used?

Issue:
ATV61/ATV71 Line reactor or DC choke requirements

Resolution:
If the DC choke is not used, a 5% line reactor must be installed on the line side of the drive.


This applies to ATV61/71 sizes:
125 HP 460V and above
75 HP 230V  and above