How can we help you today?
How is the ATV12 programmed for a 0-10Vdc analog input on AI1?
Issue:
Programming an ATV12 for a 0-10Vdc analog input on AI1
Product Line:
ATV12
Environment:
Programming
Cause:
n/a
Resolution:
The factory default is for a 0-5Vdc input. Set AI1t = 10U to accommodate a 0-10V input. AI1t is found in the IO menu and AI1 submenu.
Programming an ATV12 for a 0-10Vdc analog input on AI1
Product Line:
ATV12
Environment:
Programming
Cause:
n/a
Resolution:
The factory default is for a 0-5Vdc input. Set AI1t = 10U to accommodate a 0-10V input. AI1t is found in the IO menu and AI1 submenu.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.