Video: What can cause connection in progress issue on HMI keypad VW3A1101 with ATV212 drive?

Resolution:

  • Verify these settings using the drive’s built-in display:
    • F800 (Baud rate) = 1 → 19.2 kbps
    • F801 (Parity) = 1 → Even parity
  • Ensure the keypad firmware is version V1.1IE29 or later
  • Try replacing the control terminal block with a known working unitConfirm that F, R, and RES wires are properly connected.
  • Inspect the internal power sources. Look for short circuitsMissing or unstable voltage in terminals:
    • PP (+10 V)
    • P24 (+24 V)
After making changes, perform a power cycle on the drive.
If the issue persists, check all wiring, verify compatibility, and inspect the keypad and drive for hardware faults. Replace components if needed to isolate the problem.

    If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

    Frequently Asked Questions - Schneider Electric (se.com)

    If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

    If you are not located in North America, please contact your local Customer Care Center for assistance:

    Support | Schneider Electric Global (se.com)

    Schneider Electric USA

    Explore more

    Discuss this topic with experts

    Visit our community and get advice from experts and peers on this topic and more

    Explore more

    Need help?

    Product Selector

    Quickly and easily find the right products and accessories for your applications.

    Get a Quote

    Start your sales inquiry online and an expert will connect with you.

    Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

    Help Center

    Find support resources for all your needs, in one place.