How can we help you today?
How can the ATV212 or ATV21 be set up for start/stop on terminal and ramp to 60 Hz?
Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F.
Program the nameplate motor parameters into the following parameters:
| CODE - DESCRIPTION |
| thr - Motor thermal prot. |
| uLu - Motor rated voltage |
| F415 - Motor rated current |
| F417 - Motor rated speed |
Make the following parameter settings:
| CODE - DESCRIPTION | SETTING |
| LL - Low limit frequency | as desired |
| UL - Upper limit freq | 60 |
| Dec - Deceleration ramp time | as desired |
| ACC - Acceleration ramp time | as desired |
| CMOD - Command mode selection | 0 |
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.