How can we help you today?

How do I change the speed reference from AI3 to AI1 on an ATV312?

Issue:
Speed reference change from AI3 to AI1 on an ATV312
Product line:
Altivar ATV312
Environment:
All models, all serial numbers
Cause:
The speed reference has changed from AI3 back to AI1.
Resolution:
Go into the CTL control menu enter
Find Fr1 enter
Change Fr1 from AI3 to AI1 enter
Refer to the ATV312 Programming manual BBV46385

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings