How do you set Preset Speeds on ATV61 or ATV71 drive?
Issue:
Preset Speeds on ATV61/ATV71 drives
Resolution:
- Go into 1- Drive menu and then to 1.7 Application function menu.
- Under 1.7, go into Preset speeds submenu.
- Set 2,4,8, or 16 Preset speeds to logic inputs as desired.
Speeds for each combination of logic inputs are available at the combination table for preset speed inputs in the ATV61 programming manual.
Refer to ATV61_programming_manual_EN_1760649_08
**