How can we help you today?
How Do You Disable Input Phase Loss on an ATV61 When Using Single‑Phase Power?
When an ATV61 drive is powered by a single‑phase supply, the Input Phase Loss fault must be disabled to prevent nuisance trips. Follow the steps below to turn this function off safely.
Steps to Disable Input Phase Loss
- From the Main Menu, select Drive Menu, then press Enter.
- Navigate to Fault Management (Menu 1.8) and press Enter.
- Scroll to Input Phase Loss and press Enter.
- Set the parameter to NO (Off).
Important Notes
- This setting is required only when operating the ATV61 on single‑phase power.
- Disabling Input Phase Loss prevents the drive from detecting a missing phase condition that is expected in single‑phase operation.
- Ensure the drive is correctly sized and derated according to Schneider Electric guidelines for single‑phase applications.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.