How Do You Disable Input Phase Loss on an ATV61 When Using Single‑Phase Power?
When an ATV61 drive is powered by a single‑phase supply, the Input Phase Loss fault must be disabled to prevent nuisance trips. Follow the steps below to turn this function off safely.
Steps to Disable Input Phase Loss
- From the Main Menu, select Drive Menu, then press Enter.
- Navigate to Fault Management (Menu 1.8) and press Enter.
- Scroll to Input Phase Loss and press Enter.
- Set the parameter to NO (Off).
Important Notes
- This setting is required only when operating the ATV61 on single‑phase power.
- Disabling Input Phase Loss prevents the drive from detecting a missing phase condition that is expected in single‑phase operation.
- Ensure the drive is correctly sized and derated according to Schneider Electric guidelines for single‑phase applications.