How can we help you today?

What is the part number for the ATV71HC11N4 and ATV61HC13N4 power boards?

Issue:
Needs a Power board for ATV71HC11N4

Product line:
ATV71 and ATV61

Environment:
All models, all serial numbers

Cause:
Power board not functional

Resolution:
The Power board for these drive is VX5A1HC1113.

It is required to check the Serial number of the drive before ordering the Power Board.
If the 8th digit in the serial number is 2, the drive was built using Fuji IGBT's instead of the standard Mitsubishi IGBT's.   A drive with Fuji IGBT's requires a modified version of the Power board (VX5A1HC1113F).   IGBT, and gate driver board parts also will have an F at the end.

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.