How can we help you today?

Where can I find ATV61 programming assistance with the water solutions card VW3A3503?

Issue:
Programming and wiring up a water solution card on the ATV61 drives?

Product line:
Altivar ATV61 with water solutions option card VW3A3503.

Environment:
All models, all serial numbers

Cause:
Water Solution Card set up configuration.

Resolution:
First, go through the Pre-Configuration section in the manual.   Transducer is 0-145 PSI with 4-20mA Output. There are 2 additional External pumps.   Go to Page 86 to set System Units =1 (Imp, Gallon and Degree Fahrenheit)   Water Solutions/Expansion/PID PID Ref Local (Local PID reference will appear under Water Solutions menu) PID Max Ref 100 psi PID Feedback  Drive AI2 PID Gain 50 PID Integral 1   Water Solutions/Expansion/Sensors Outlet Transducer Maximum   145 psi Pressure Units PSI   Water Solutions/Expansion/Start Set Setpoint Ramp  5.0   Water Solutions/Expansion/Stage Number of External Pumps 1 Stage Speed  50 hZ  Jumper: +24 to CI_LI54 External Pump 1 No Fault +24 to CI_LI55 External Pump 2 No Fault +24 to CI_LI57      Auto enable   The Feedback Pressure(monitored under water Solution menu) must be lower than the Start Pressure(programmed in Start Set) when closing CI_LI57 and want the unit to start.

Wiring examples:
CLI57= auto enable or start
CLI58= fault reset

Transducer input
AI2= Analog input on the drive
AI52 and AI51= analog inputs on the water solutions card

Fault feedback inputs from aux pump overload relays
CLI54= for fault input for Aux pump 1
CLI55= for fault input for Aux pump 2
CLI56= for fault input for Aux pump 3

Aux pump outputs
CLO51= Aux output for pump 1
CLO52= Aux output for pump 2
CLO53= Aux output for pump 3

Status outputs from the WSC
CLO55= Run status
CLO56= Fault status

Jockey pump option
CLO56= Jockey or priming pump output


Water Solution Control Card User manual

Schneider Electric USA

Attachment(s)

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.