How can we help you today?

What can be done when variable speed drives or VFDs are causing motor bearing failures?

Issue:
What can be done when VFDs are causing bearing failures?

Product line:
Altivar All

Environment:
All models, all serial numbers
Cause:
Shaft currents causing the motor bearings to weld.

Resolution:
This phenomena is inherent to VFD use.  On the VFD, try lowering the switching frequency to reduce effects but not resolve it.

Other suggestions include:
installing shaft grounding systems
installing insulated bearings
adding a dv/dt filter to couple less voltage to the rotor
adding a common mode filter
verify good grounding from the motor directly back to the VFD

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.