How can we help you today?
How do I configure the R1 relay on an ATV12 drive to close when the motor is running?
Resolution:
The Altivar 12 (ATV12) drive includes one programmable relay with NO and NC contacts, located on terminals R1A, R1B, and R1C:
- Normally Open (NO): R1A – R1C
- Normally Closed (NC): R1B – R1C
The relay supports both 120 VAC and 24 VDC control circuits.
To have the R1 relay indicate that the motor is running, configure the relay as follows:
- Navigate to:
COnF → FULL → I_O- → r1 - Set the r1 parameter to rUn (Run status).
When the drive is supplying output voltage to the motor (motor running), the R1A–R1C normally open contact will close.
For additional details, refer to the ATV12 User Manual (BBV28581).
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.