Video: How can I obtain run status from ATV212 and S-Flex drives?

Article available in these languages:

Resolution:

You can retrieve the run status from ATV212 and S-Flex drives by wiring to specific terminals and ensuring the correct parameter settings are configured.

ATV212 Open Style Drives

  • Connect directly to terminals RYA and RYC.
  • Set parameter F130 = 14 (Drive Running).
  • When a run command is active, the relay contacts change from normally open to closed.
  • The contacts return to open when the run command is removed or if a fault stops the drive.

S-Flex Enclosed Drives (AFC or Bypass Mode)

  • Run status is available at terminals 13 and 14 when operating in AFC or Bypass mode.

S-Flex Enclosures (June 2011 and Earlier)

  • Use RYA (terminal 11) and RYC (terminal 12) on the drive.
  • Set F130 = 14 (Drive Running).
  • Contacts close when the drive is running and reopen when stopped or faulted.
  • In Bypass mode, run status is also available at terminals 13 and 14.

S-Flex Drives with LON Option Card

  • RYA and RYC terminals are not available.
  • Run status in AFC mode must be obtained through the network communication system.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.