How can we help you today?

Where can I find basic programming information for ATV32?

Issue:
Looking for basic programming information for ATV32

Product Line:
Altivar ATV32

Environment:
All

Cause:
Programming configuration set up

Resolution:

CONF>FULL>SIM

bFr= Base motor frequency 60hz
nPr= HP of he motor
UnS= Rated motor voltage
nCr= Rated motor current (motor FLA)
FrS= Rated motor frequency
nSP= Ratd motor speed (rpm's on motor nameplate)
tFr= Max frequency
ItH= Motor thermal current (match motor FLA)
ACC= Acceleration (ramp up) time
dEC= Deceleration (ramp down) time
LSP= Low speed
HSP= High speed

Schneider Electric USA

Attachment(s)
ATV32 Programming Manual.pdf [3.38 MB]
ATV32 quick start guide.pdf [1003.56 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings