How is Accumulated Power Consumption (APH) calculated on ATV61 and ATV71 drives?
The APH (Accumulated Power Consumption) value is calculated based on the motor's electrical consumption as measured by the drive, using parameters such as motor current and motor voltage.
Because the measurement represents the electrical power supplied to the motor, it includes the motor's mechanical losses.
The drive does not measure reactive power when calculating APH. As a result, the estimated accuracy of the APH value is approximately 10%. Losses within the variable speed drive (VSD) are considered insignificant relative to this level of accuracy.
Important: APH is intended as an estimated energy-consumption value. It is not recommended for electrical billing or other applications requiring revenue-grade energy measurement.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.