How can we help you today?
ATV61: Is there a way to monitor or read the DC bus on the drive HMI?
Issue:
Looking to monitor or read the DC bus on the ATV61 drive HMI.
Product Line:
Altivar 61/71 ATV61 ATV71
Environment:
All
Cause:
Limited access to terminals
Resolution:
There are no monitoring options for reading the DC Bus from the drive HMI.
In the monitor menu it will display "Mains Voltage".
To calculate the DC Bus voltage:
If you multiply this value by 1.414 (sq root of 2) the result will be the value of the DC bus.
However, the drive does a calculation with the DC bus voltage to determine the mains voltage (line supply).
Looking to monitor or read the DC bus on the ATV61 drive HMI.
Product Line:
Altivar 61/71 ATV61 ATV71
Environment:
All
Cause:
Limited access to terminals
Resolution:
There are no monitoring options for reading the DC Bus from the drive HMI.
In the monitor menu it will display "Mains Voltage".
To calculate the DC Bus voltage:
If you multiply this value by 1.414 (sq root of 2) the result will be the value of the DC bus.
However, the drive does a calculation with the DC bus voltage to determine the mains voltage (line supply).
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.