What is the CFF fault on the ATS48 soft starter and what causes it?
Issue:
The CFF fault on an ATS48 soft starter indicates an internal configuration error.
Resolution:
This fault can often be resolved by restoring the soft starter to its factory settings and reconfiguring the application parameters.
Reset the Soft Starter to Factory Defaults
- Go to the drC menu.
- Navigate to the FCS parameter.
- Change the value to YES.
- Press and hold the Enter key for 2 seconds to confirm the factory reset.
- Reprogram the soft starter with the required application settings.
- Cycle power to the unit.
- Apply a new run command.
If the Fault Remains
If the CFF fault continues after performing a factory reset and reprogramming the device, the issue may be related to a hardware failure. In this case:
- Replace the control board, if applicable.
- If the control board is not replaceable or the issue persists, replace the soft starter.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.