Can a 90degC conductor be used in a QED 2 or QED 6 switchboard?

Issue:
Use 90 °C wires in a switchboard

Product Line:
Switchboards

Environment:
QED
Speed
CMM
PZ4

Resolution:
90degC conductors can be used for 80% and 100% applications but must be sized for 75 °C cable capacity. However, 90 degC wire should be used in 100% applications, but still needs to be sized to 75 °C cable capacity.