What is the Wait Time to Reset (SnbF) on an ATS22?

Resolution:
SNBF cannot be cleared by powering down the Softstart.  One way to clear the fault is to wait with power still applied to the Softstart.
The wait time depends on the frame size. The control power must be on to run the timer.
Frame size A is 5 minutes.
Frame size B, C, D and E is 15 minutes.