Powerlink G3 Modbus Direct Breaker Control ASCII Examples
Issue:
Modbus direct breaker control integration.
Product Line:
Powerlink G3 Main panel direct breaker control Modbus Example
Environment:
Modbus
Cause:
ALL ASCII strings are to be followed by <CR><LF> per Modbus standard. The ":" start character is shown in the string.
Resolution:
See attached reference guide for Modbus example:
Modbus direct breaker control integration.
Product Line:
Powerlink G3 Main panel direct breaker control Modbus Example
Environment:
Modbus
Cause:
ALL ASCII strings are to be followed by <CR><LF> per Modbus standard. The ":" start character is shown in the string.
Resolution:
See attached reference guide for Modbus example:
| Bus_Breaker # | Trim # (Reference) | ON String | OFF String |
| 0L_1 | 1 | :01050BB7FF0039 | :01050BB7000038 |
Released for: Schneider Electric USA