Why Does the IP Address Reset to 0.0.0.0 After Power Cycling an ATV61 or ATV71 with a VW3A3316 Ethernet/IP Card?

Resolution:
When Forced Local Assignment is assigned to a logic input and that input is active, the IP address and subnet mask may reset to their default value of 0.0.0.0 after the drive is power cycled.

To troubleshoot:

Go to Menu 1.9 [Communication] and check the Forced Local Assignment setting.

When using the VW3A3316 Ethernet/IP option card, verify that Forced Local Assignment is not assigned to a logic input. Then confirm the required IP address and subnet mask settings before power cycling the drive.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.