Issue:
How to disable Ethernet Network connectivity in Tesys T controllers?

Product Line:
IEC Contactors and Overload relays

Environment:
Tesys T motor management system

Resolution:
There is no setting in the software to disable the ethernet network. On the Tesys T you actually use hardware to disable the network. There are two dials on the face of the device, a Tens dial and a Ones dial. On the Ones dial, choose the Disabled setting and then power cycle the Tesys T. The device will no longer look for a network and will not give the Network settings warning.