How can we help you today?
What poles can you primary inject to test a Y frame (6 or 8 pole) Masterpact breaker?
Product Line:
Masterpact NW, NT
Resolution:
8 pole breaker: Poles 4, 5 and 7 when looking at the front. These poles will power up the Micrologic trip unit.
6 pole breaker: Poles 2, 3 and 5 when looking at the front. These poles will power up the Micrologic trip unit.
All poles do meter current, so any pole can be tested if you already have the trip unit externally powered up.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.