How is the sleep/wake (low speed timeout) programmed on the ATV212 drives?
Issue:
Sleep/wake operation (low speed timeout) programmed on the ATV212 drives.
Resolution:
The sleep/wake threshold is defined as LL + F391.
The time period to trigger sleep mode is F256.
If the drive operates at or below the threshold (LL + F391) for a period of time (F256), the drive will decelerate to a stop and flash LStP. It will remain stopped until the speed reference again exceeds the threshold (LL + F391). The drive will then accelerate to the new reference.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.