What ambient conditions are acceptable for operation and storage of Powerpact H, J, and L frame circuit breakers?

Article available in these languages: Spanish

Issue:
What considerations must be made for ambient temperature, humidity, altitude, and vibration when storing or operating Powerpact H, J, and L frame circuit breakers?

Product Line:
Circuit Breakers

Resolution:
PowerPact™ H-, J-, and L-frame circuit breakers may be used at ambient temperatures between -13°F and 158°F (-25 °C and +70 °C). For temperatures higher than 104° F (40° C) inside the enclosure, devices must be derated.  See attachment for specific rerating factors for both thermal-magnetic and Micrologic (electronic) trip breakers.  Circuit breakers should be put into service under normal ambient operating-temperature conditions.

Altitude does not significantly affect the characteristics of PowerPact H-, J-, and L-frame circuit breakers circuit breakers up to 6560 ft (2000 m). Above this altitude, it is necessary to take into account the decrease in the dielectric strength and cooling capacity of air.
At altitudes greater than 6560 ft. (2000 m), rerating factors apply; see attachment for details.

It is recommended that the equipment be cooled or heated to the proper operating temperature and kept free of excessive vibration and dust, and be protected from water intrusion and condensation.

See attachment for recommendations regarding vibration, humidity, frequency, and storage.

Schneider Electric USA

Attachment(s)
Operating Conditions Powerpact H, J, L - 0611CT1001.pdf [203.88 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings