How can we help you today?

What is a XCSZP7012?

Product Line:
Machine safety switch

Cause:

Purchasing and identification

Resolution:

This is the switch portion of a coded magnetic switch. The switch will be marked with the XCSZP7012 part number but it is not sold without the magnet.
Complete part number for the switch with magnet is XCSDMP7012.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.