What causes a PHF (input phase loss) fault on ATV61 and ATV71 drives?

Resolution:

A PHF fault on ATV61 and ATV71 drives indicates an input phase loss, meaning one or more supply phases are missing.

How it works:

  • The drive detects a missing input phase and triggers the PHF fault.
  • If one or more phases are lost while the drive is running, the drive may continue operating temporarily and then stop due to another fault (such as USF – undervoltage fault).
  • In some cases (e.g., when the motor is acting as a generator), the fault may not be detected immediately.
  • The PHF fault condition is stored in memory (EEPROM) during operation.

Important notes:

  • The IPL (Input Phase Loss) parameter can be set to NO to disable phase loss detection when using DC bus supply (typically for 230 V or 480 V ranges).
  • Some smaller drives (230 V models up to 7.5 kW) may have IPL = NO by default, as they are designed to run on single-phase input.

Common causes:

  • Loss of one input phase
  • Blown or open fuse
  • Incorrect power supply wiring
  • Using a single-phase supply on a drive configured for three-phase input

Recommended solutions:

  • Verify all power connections are secure
  • Check and replace any blown fuses
  • Ensure the drive is supplied by a proper three-phase network
  • If appropriate for the application, disable the input phase loss detection (IPL = NO)

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.