What causes a PHF (input phase loss) fault on ATV61 and ATV71 drives?
Resolution:
A PHF fault on ATV61 and ATV71 drives indicates an input phase loss, meaning one or more supply phases are missing.
How it works:
- The drive detects a missing input phase and triggers the PHF fault.
- If one or more phases are lost while the drive is running, the drive may continue operating temporarily and then stop due to another fault (such as USF – undervoltage fault).
- In some cases (e.g., when the motor is acting as a generator), the fault may not be detected immediately.
- The PHF fault condition is stored in memory (EEPROM) during operation.
Important notes:
- The IPL (Input Phase Loss) parameter can be set to NO to disable phase loss detection when using DC bus supply (typically for 230 V or 480 V ranges).
- Some smaller drives (230 V models up to 7.5 kW) may have IPL = NO by default, as they are designed to run on single-phase input.
Common causes:
- Loss of one input phase
- Blown or open fuse
- Incorrect power supply wiring
- Using a single-phase supply on a drive configured for three-phase input
Recommended solutions:
- Verify all power connections are secure
- Check and replace any blown fuses
- Ensure the drive is supplied by a proper three-phase network
- If appropriate for the application, disable the input phase loss detection (IPL = NO)