How can we help you today?
Sepam Series 80 Firmware Cycle Time
Issue:
Clarify the firmware execution cycle behavior for Sepam Series 80 protection relays and what functional groups execute each cycle.
Product Line:
Sepam Series 80
Environment:
Sepam Series 80 protection relays
Firmware execution of protection, logic, I/O, and measurement functions
Cause:
Project and commissioning teams require a concise description of the relay’s deterministic execution cycle to support coordination studies and to estimate end‑to‑end behavior of protection and control logic.
Resolution:
- Sepam Series 80 firmware operates cyclically and deterministically, running protection algorithms, control logic, I/O scanning, and device self‑checks in a repeating execution loop.
- Fast functions executed every cycle include the protection elements, logic input scanning, control logic (including the logic equation editor/Logipam constructs), and logic output updates, alongside device self‑diagnostics.
- Measurement and other slow/housekeeping tasks are distributed across cycles.
- When a quantified timing value is required for an engineering study, perform a bench verification on a representative relay and firmware build by toggling a digital input, driving a simple control logic action, and measuring the repeatable delay at a digital output or in time‑tagged event data. Record the firmware version/build and configuration with the results.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.