How can we help you today?

What is the pinout for connecting to a 984 cpu using modbus?

Issue:

What is the pinout for connecting to a 984 CPU using Modbus?

Facts and Changes

9 pin to 9 pin

Resolution:

The Modbus (DB9 to DB9) pinout is as follows:
Pins 2 and 3 will cross,
Pin 5 Straight through,
Pins 4 and 6 will cross,
Pins 7 and 8 jumper back to each other on both sides.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.