How can we help you today?

We have an softstarter ATS48C48Q that is displaying the OCF code. We have been following the instruction on User´s Manual : checking the motor and wiring.

Goals and Symptoms

We have a softstarter ATS48C48Q that is displaying the OCF code. We followed the instruction on User´s Manual : Checking the motor and wire isolation, by-pass circuits testing, and the others recommendations. We did not find anything that explains the situation. The OCF code is displayed randomly, in anytime, inclusive without the RUN command order and without main power supply on L1-L2-L3 . Could you say us what another causes are possible? We already have changed the control board, but the result is the same : the OCF code continues displaying.

Facts and Changes

OCF

Causes and Fixes

In case of OCF error without Run command , there is several potential damage on the component

  • The power board ( bad soldering , component issue on channel measurement current)
  • Thyristor damage
  • Current sensor

These component could be change OR  change completely the product

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.