How do I change the watchdog timeout value in Unity Pro?

To change the watchdog timeout value, go to the Project Brower and right click on the MAST, FAST or AUX directory and choose <Properties>. The following box appears:
Properties of MAST


The Watch Dog timeout value must be greater than the period value (specified time in which the master task must be executed).
System Bit %S11 indicates watchdog overflow. This bit is set to 1 when the task execution time becomes greater than the maximum execution time (watchdog timout value).