Which IODDT data type would I use for an M340 analog input module that includes the input value and other channel information?

Issue:

Which IODDT data type would I use for an M340 analog input module that includes the input value and other channel information?

Product Line:

M340 analog input module

Resolution:

The IODDT for all channel properties is T_ANA_IN_BMX..
This Data Type will yield all of the channel's properties and diagnostic information.
If you only want the channel VALUE and CH_ERROR properties you can use the T_ANA_IN_GEN  Data Type.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.