How can we help you today?
What does "basic OS loader invalid checksum" displayed on a Quantum 140CPU6XX indicate?
Issue:
What does "basic OS loader invalid checksum" displayed on a Quantum 140CPU6XX indicate?
Product Line:
Quantum
Resolution:
This error can be seen if there was an interruption to the Executive Flash process. Sometimes the PLC is recoverable and sometimes it is not. To recover, some of the actions listed below can be attempted. Remove any PC cards installed in the PLC and any cards other than the PLC and PS from the back plane. If available, try a different power supply and back plane.
- Power cycle.
- Power off, press and hold the ESC key through power up.
- Press the Restart button next to the battery.
- Use the OS Loader to connect to the PLC using either Modbus or MB+, set to address 1 and attempt to flash firmware.
- Power off, remove battery, remove from back plane, let sit 120 minutes and power on.
If after the above actions the PLC does not recover, it must be returned for repair/ exchange.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.