Power Monitoring Expert (PME) Vista message: Unexpected program status 'Bad'

Issue
In Power Monitoring Expert (PME) Vista application, When linking a Numeric Object to a Modbus source created with the MDI or DTE, the object is surrounded by an orange box. The message when hovering over the box is:
Vista error
"Communication error. The source returned an unexpected result. 'Unexpected program status 'Bad'.' The value has not been read."

Management Console will also provide an error:
MC Error
Invalid Modbus Register Address '400000'.

Product Line

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024


Environment
Modbus Device Importer
Device Type Editor
PME Vista


Cause
"Modbus Device Importer (MDI)" is a tool used in versions prior to PME 9.x. It was replaced in PME with the "Device Type Editor (DTE)". This tool is used to create custom Modbus and OPC device drivers. If the error is seen, there is an invalid register address configured in the device driver that is causing the "bad" status.

Solution
Open the affected translator file in the Modbus Device Importer (Management Console>Tools>Modbus Device Importer OR Management Console > Tools> System> Device Type Editor). Once open, find the invalid Modbus address referenced in the Management Console error; in this case, it is registered as '400000'. Either reassign the correct Modbus address or remove the register completely from the translator, save, and update the device type.

Recommendation
If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Upgrade details

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.