What is the Modubs Register for Digital Input 1 (DI1) for a 7650

Issue

What Modbus register should be used to read Digital Input 1 (DI1) on an ION7650 meter?

Product Line

PowerLogic ION7650

Environment

Modbus (RTU or TCP)

ION Setup or ION Designer

External SCADA/PLC/RTU

Cause

Not all ION modules have a hard‑coded Modbus register. DI1 on the ION7650 is one such case.

Resolution

  • Map the DI1 module’s State output to a Modbus Slave register, then read that Modbus holding register from your master.

Note

ION7650 is discontinued, the recommended Schneider Electric replacement  is ION9000 series.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings