How can we help you today?

Can the ION7700 be calibrated to the ANSI C12.20 class 0.2 accuracy standard?

No, certain energy levels meet the 0.2 accuracy standards (kVAh, kWh), but others fall short (kVARh). Since all parameters do not meet the standard it is not possible to classify the meter with the C12.20 class 0.2 accuracy standard.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.