What is the Maximum Real Energy (kWh) Accumulation Value Possible on an Enercept or Energy Meter?

Although, the real energy consumption is stored as a 32-bit floating point value and is held across two registers, the max kWh value is not equal to 4,294,967,296 kWh (which is 2^32).  Instead, the maximum real energy accumulation is dependent upon the model of Enercept or energy meter. See the table below.

CTkWh/CountAccumulator Max kWH
1000.007833,554,432
2000.1562567,108,864
300/4000.03125134,217,728
8000.0625268,435,456
16000.125536,870,912
24000.251,073,741,824