“Use GPS Quality Flag,” has been introduced in the Setup Register for ION8600 version 332 ( v332).
Issue
For some reason, unexpectedly the meter (ION8600) stops communicating.
Product Line
ION8600
ION Setup
Environment
Configuration
Cause
The clock source couldn’t sync.
Resolution
A new setup register has been added to the clock module on the ION8600 v332. This register is called Use GPS Quality Flag and provides two configuration options: Use Flag and Ignore Flag.
In previous firmware versions, meters configured to synchronize with a GPS time source would only accept time synchronization when the GPS was locked to a satellite. If the GPS source became unlocked, the meter would stop accepting time sync signals until the lock was restored.
Go to ION Setup Advanced configuration > Clock Modules > Setup register. See highlighted on figure 1 below.
Fig. 1
To select one of the behaviors: Highlight CL1 Use GPS Quality Flag > Edit > Then select either one. See figure 2 below:
This new feature allows users to choose between two behaviors:
Use Flag: The meter will only accept time synchronization if the GPS source quality flag indicates a locked state.
Ignore Flag: The meter will accept time synchronization regardless of the GPS source quality flag state.
Fig. 2
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.