Testing Demand Period on ION8600 Using PME/Designer

Issue:

The sliding window demand modules in the ION Revenue Test Framework cannot be reset with a push-button. The “Demand Reset” button resets the values but does not reset the period, causing testing delays.

Product:

ION8600 Meter
ION Revenue Test Framework
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment:

  • ION8600 meters configured with the ION Revenue Test Framework
  • Sliding Window Demand modules used for demand testing
  • PME/ION Designer for configuration and testing

Cause:

The sliding window demand modules are synchronized with the meter’s system clock and only reset at fixed intervals (e.g., 00, 15, 30, 45 minutes for a 15-minute period). This design prevents manual reset of the demand period, limiting flexibility during testing.

Resolution:

Workaround: Modify the ION Revenue Test Framework as follows:

1- Add a Pulse Merge module:

    • Connect Pulse In 1 to Test Dmd Rset of the Test Dmd Rset module.
    • Connect Pulse In 2 to CNV1 On Pulse output of the Test Mode Rset module.

2- Add a One-Shot Timer module:

    • Link its Sync input to the Pulse Out of the Pulse Merge module.

3- Connect the Trigger output of the One-Shot Timer to the Sync input of both KW sd del T and KW sd rec T modules.

1
* red box indicates added modules

Permanent Fix:
Download and apply the corrected framework template for the affected meter models:

  • 8600A_V330_FAC-35S_V3.3.0.0.4.fwn
  • 8600A_V330_FAC-35S-PQ_V3.3.0.0.5.fwn
  • 8600A_V330_FAC_V3.3.0.0.4.fwn
  • 8600A_V330_FAC-PQ_V3.3.0.0.5.fwn
  • 8600B_V330_FAC-35S_V3.3.0.0.4.fwn
  • 8600B_V330_FAC_V3.3.0.0.4.fwn
  • 8600C_V330_FAC-35S_V3.3.0.0.4.fwn
  • 8600C_V330_FAC_V3.3.0.0.4.fwn

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.